Procure Direct are pleased to be able to supply a lighting plan based on our products we supply and install. When we undertake an installation we will not only supply you with a energy saving calculation but we will also give you a lighting design that shows the light levels and details of the products we are supplying. This will show you what light levels you will get in classrooms and office and in warehouses. You will find a number of examples of plans we are created for clients. These show not only what can be achieved with standard LED, but also what can be achieved with our new design of LED technology
C90 - C270
C0 - C180


Height of Room: 6.000 m, Mounting Height: 6.000 m, Maintenance factor: 0.80
Values in Lux, Scale 1:386
Surface
%
Eav [lx]
Emin [lx]
Emax [lx]
u0
Workplane
/
269
115
326
0.429
Floor
27
257
99
317
0.386
Ceiling
80
59
31
74
0.525
Walls (4)
27
108
35
220
/

Workplane
Height: 0.750m
Grid: 128x128 Points
Boundary Zone: 0.500m
Illuminance Quotient (according to LG7):
Walls/Working Plane: 0.386
Ceiling/Working Plane: 0.219


Luminaire Parts List
No
Pieces
Designation (Correction Factor)
Luminaire [lm]
Lamps [lm]
P [W]
1
36
PD-TGD-150W (Type 1)* (1.000)
11,841
11,829
151.0
Total: 426,288
Total: 425,844
5436.0
*Modified Technical Specifications
Specific connected load: 4.03 W/m² = 1.49 W/m²/100 lx (Ground area: 1350.00m²)
Photo showing original 400 watt fittings
Photo taken after LED install with 150 watt fittings
C90 - C270
C0 - C180


Height of Room: 2.800 m, Mounting Height: 2.800 m, Maintenance factor: 0.80
Values in Lux, Scale 1:78
Surface
%
Eav [lx]
Emin [lx]
Emax [lx]
u0
Workplane
/
323
220
399
0.683
Floor
20
263
149
337
0.566
Ceiling
70
60
41
66
0.688
Walls (4)
27
140
46
291
/

Workplane
Height: 0.750m
Grid: 32x32 Points
Boundary Zone: 0.500m
Illuminance Quotient (according to LG7):
Walls/Working Plane: 0.429
Ceiling/Working Plane: 0.186


Luminaire Parts List
No
Pieces
Designation (Correction Factor)
Luminaire [lm]
Lamps [lm]
P [W]
1
9
PD-600X600-27W(Type 1)* (1.000)
2536
2536
27.0
Total: 22,823
Total: 22,824
243.0
*Modified Technical Specifications
Specific connected load: 4.50 W/m² = 1.40 W/m²/100 lx (Ground area: 54.00m²)
Before installation
After installation